A control transformer takes a 240 V or 480 V supply down to 120 V or 240 V for contactors, relays, pilot lights, timers and PLC inputs. Separating the control circuit from the main supply keeps a fault on one side from reaching the other, and lets a panel be worked on safely.
The BK3 series runs BK3-40, 63, 100, 160, 250, 300, 400, 630, 800, 1000, 1600 and 2500. Footprints go from 78 × 70 mm at the small end to 205 × 260 mm at the top, with slotted holes so a replacement usually fits the existing drilling pattern. Standard windings are 240/480 V to 120/240 V; other ratios are wound to order.
A contactor coil draws several times its holding current for the first few cycles. Sizing on sealed VA alone is the common mistake: the transformer saturates on every pull-in, the output dips, and contactors chatter. Add the sealed VA of all loads, then add the largest single inrush as though it were continuous, and choose the frame above that figure.
An isolated unit has separate windings, so the secondary can be earthed independently and the circuits are galvanically separated. An autotransformer shares one winding: smaller and cheaper, no isolation. Any circuit a person may touch, or that feeds a PLC input, belongs on an isolated unit.
Smaller frames use combination screw terminals; larger frames use stud terminals with a link bar for series or parallel primary connection. Confirm the supply voltage first — a dual-primary unit wired for the wrong supply puts double the voltage on the secondary.
Can I get a non-standard voltage?
Yes. Windings are made to order; send the primary and secondary voltage required.
Why does a contactor chatter on a 100 VA transformer?
Inrush is being drawn from a frame that is too small. Check the coil's inrush VA, not its sealed VA.
Is a control transformer an isolation transformer?
The isolated version is. The autotransformer version is not.