A dry-type transformer has no oil. The windings are cast in resin or impregnated and cooled by air, which removes the tank, the oil testing and the containment. What it costs instead is size: a dry unit is larger and heavier than an oil unit of the same rating.
Three-phase units from 0.5 kVA to 300 kVA, with winding voltages up to 500 V and 50 or 60 Hz operation. Ratios, vector groups and tappings are made to order, so the unit is built against the project specification rather than picked from a stock list.
Indoor plant rooms, basements, hospitals, data centres and food production — anywhere a leak would be a serious event. No oil means no bunded floor, no periodic sampling and no fire separation. The trade is space: allow clearance for convection, and expect a larger frame than the oil equivalent.
Whether the winding is cast resin or impregnated (cast resin handles damp and dusty air better), the IP rating of the enclosure, the impedance, and the permitted temperature rise. A lower temperature rise buys insulation life and costs money — worth fixing at specification stage rather than after installation.
An open unit belongs in an indoor plant room with adequate ventilation; outdoors it needs a weather-rated enclosure. Ambient temperature and altitude affect permissible loading, so state them when enquiring rather than assuming standard conditions.
Can it be installed outdoors?
Only inside an enclosure rated for the weather.
Does it need maintenance?
Less than an oil unit — no oil sampling. The routine work is cleaning the windings and checking terminal torque.
Is it quieter than an oil transformer?
No. Dry units are generally louder at the same rating. If the room is occupied, ask for the sound level at specification stage.